F-gas regulations for refrigeration, air conditioning and heat pumps
Fluorinated greenhouse gases (F-gases), mainly the HFC refrigerants in chillers, cold rooms, air conditioning, heat pumps and vehicle refrigeration, are controlled in Great Britain by the retained F-gas Regulation and the Fluorinated Greenhouse Gases Regulations 2015. Equipment owners must have leak checks at set intervals, use certified engineers, keep records and avoid banned refrigerants; producers and importers need quota. The next HFC phase-down step cuts GB supply from 1 January 2027. Northern Ireland applies the EU's 2024 F-gas Regulation.
At a glance
- Who must comply
- Operators of equipment containing F-gas (anyone with commercial refrigeration, air conditioning, heat pumps, refrigerated vehicles or fire suppression); installers and service engineers; importers and sellers of F-gas and pre-charged equipment.
- Thresholds
- Leak checks from 5 tonnes CO2e of refrigerant (for example about 1.3kg of R404A or 3.5kg of R134a); hermetically sealed units exempt below 10 tCO2e.
- Next key date
- 1 January 2027: GB HFC quota falls by 22.6%, reducing supply of high-GWP refrigerants; EU rules in Northern Ireland continue to tighten.
- Regulator
- Environment Agency (GB enforcement and quota), with SEPA and NRW in Scotland and Wales; NIEA in Northern Ireland; Defra sets policy.
- Maximum penalty
- Civil penalties under the 2015 Regulations of up to £200,000 per breach, with £100,000, £50,000 and £10,000 tiers for specific duties such as leak checks, certification and records.
- Where to do it
- No registration for equipment owners; certification through approved bodies; quota and reporting through the Environment Agency's HFC registry.
This probably applies to you if
- You own or operate cold rooms, display cabinets, chillers, air conditioning, heat pumps, refrigerated transport, process cooling or fire suppression containing HFCs
- You install, maintain, service, leak-check or decommission that equipment
- You import, sell or install pre-charged equipment or bulk refrigerant in Great Britain
- You operate equipment in Northern Ireland, where the EU F-gas Regulation 2024/573 applies
- You plan new equipment and need to avoid refrigerants that are banned or being phased down
The legal framework
In Great Britain the EU F-gas Regulation (517/2014) was retained after Brexit and amended to work as GB law, with the Fluorinated Greenhouse Gases Regulations 2015 providing enforcement and civil penalties. It covers HFCs, PFCs and SF6, measured in tonnes of CO2 equivalent (tCO2e), which is the mass of gas multiplied by its global warming potential (GWP). In Northern Ireland the EU's replacement Regulation (EU) 2024/573 applies under the Windsor Framework, with a faster phase-down and more bans.
Defra consulted in 2025 on changing the GB phase-down and adding new restrictions. In May 2026 it confirmed it would not legislate in 2026 to change the phase-down steps due from 1 January 2027 and would set out next steps later. Until new regulations are made, the retained rules below apply.
Leak checks for equipment owners
| Refrigerant charge | Leak check at least every | With an automatic leak detection system |
|---|---|---|
| 5 to under 50 tCO2e | 12 months | 24 months |
| 50 to under 500 tCO2e | 6 months | 12 months |
| 500 tCO2e or more | 3 months | 6 months; a leak detection system is mandatory (except pre-2017 switchgear and organic Rankine cycles) |
Hermetically sealed equipment is exempt unless it contains 10 tCO2e or more. Leak detection systems must themselves be checked annually (every six years on switchgear). Any leak found must be repaired without undue delay and re-checked within a month. Converting charge to tCO2e: a system holding 10kg of R410A (GWP 2,088) is 20.9 tCO2e, so it needs six-monthly checks.
Tip: your maintenance contractor should already hold the F-gas records and schedule the checks, but the legal duty sits with the operator. Ask for the log each year.
Records, certification and labelling
- Records: for each item of equipment subject to leak checks, keep the quantity and type of F-gas, amounts added or recovered, the identity of the certified company that serviced it, dates and results of leak checks, and decommissioning details. Keep them for at least five years and make them available to the regulator.
- Certification: anyone who installs, services, maintains, repairs, leak-checks or decommissions F-gas equipment must hold a personnel qualification (for example City & Guilds 2079 or equivalent), and companies carrying out those activities must hold a company certificate from an approved body such as Refcom or Quidos.
- Labelling: equipment must carry a label stating the F-gas type, quantity and tCO2e; sellers of refrigerant may only supply to certified businesses.
- Recovery: F-gas must be recovered by certified personnel before equipment is disposed of, and sent for reclamation or destruction.
Bans and the HFC phase-down
The phase-down limits the quantity of HFCs, in tCO2e, that producers and importers can place on the GB market each year; it is 31% of the baseline for 2024 to 2026 and falls to 24% from 1 January 2027 (a 22.6% cut) and to 21% in 2030. Quota holders register on the Environment Agency's HFC registry and report annually. Importers of pre-charged equipment must hold quota authorisations.
Key bans in Great Britain include:
- servicing refrigeration equipment with a charge of 40 tCO2e or more using virgin refrigerant with a GWP of 2,500 or more (such as R404A) since 2020; reclaimed or recycled gas may be used until 2030;
- new stationary refrigeration using refrigerants with a GWP of 2,500 or more (with exceptions below -50°C) since 2020;
- new single-split air conditioning containing less than 3kg of F-gas with a GWP of 750 or more from 1 January 2025.
Northern Ireland follows the EU 2024 Regulation, which adds bans on high-GWP refrigerants in new heat pumps and air conditioning in stages from 2027 and an eventual HFC phase-out by 2050.
How to comply, step by step
Inventory your equipment
Every refrigeration, air conditioning, heat pump, vehicle and fire suppression unit with its refrigerant type, charge in kg and tCO2e.
Set the leak check schedule
Apply the 5, 50 and 500 tCO2e thresholds and halve the frequency where leak detection is fitted; diarise the checks.
Use certified contractors
Check the engineer's qualification and the company's certificate before any work on the system.
Keep the F-gas log for five years
Charges, top-ups, recoveries, leak checks and repairs, with the contractor's details.
Plan refrigerant replacement
Identify equipment on R404A, R410A and other high-GWP gases, budget for retrofits or replacement before supply tightens in 2027 and bans bite.
Enforcement and penalties
The Environment Agency (with SEPA and NRW) enforces the GB rules using civil penalties under the 2015 Regulations. Schedule 4 sets a default maximum of £200,000 per breach, with £100,000 for most leak-check, certification, recovery and labelling duties, £50,000 for record-keeping and reporting failures, and £10,000 for certain quota and administrative breaches. The Agency also carries out spot checks on supermarkets, cold stores and installers, and prosecutes the sale of refrigerant to uncertified buyers.
How it differs across the UK
- E England
Retained F-gas Regulation 517/2014 and the 2015 Regulations, enforced by the Environment Agency, which also runs the GB HFC registry and quota system.
- W Wales
Same GB rules, enforced by Natural Resources Wales alongside the Environment Agency's GB-wide quota administration.
- S Scotland
Same GB rules, enforced by SEPA.
- NI Northern Ireland
Regulation (EU) 2024/573 applies under the Windsor Framework, enforced by NIEA: a steeper HFC phase-down, additional bans on high-GWP gases in new equipment from 2027 and a phase-out of HFCs by 2050.
Key dates
-
GB HFC phase-down: quota falls to 24% of baseline (a 22.6% reduction in supply)
-
Possible GB F-gas reforms following Defra's 2025 consultation (no legislation yet)
-
GB HFC phase-down: quota falls to 21% of baseline; end of the reclaimed-gas service exemption for high-GWP refrigerants
Dates marked “Proposed” are announced or consulted on but not yet law. See the full deadlines calendar.
Penalties and enforcement
| Breach | Penalty | Applies in | |
|---|---|---|---|
| Failing to carry out leak checks, use certified personnel, recover gas or label equipment (most 2014 Regulation duties) | Civil penalty of up to £100,000 per breach | EWS | Source |
| Failing to keep or produce F-gas records, or to report | Civil penalty of up to £50,000 per breach | EWS | Source |
| Other breaches of the F-gas rules, including placing HFCs on the market without quota | Civil penalty of up to £200,000 per breach (default maximum) | EWS | Source |
Compliance checklist
Where to do it: official services
-
Fluorinated gases (F gases): guidance collection
Guidance
The GB guidance on leak checks, records, certification, bans, quota and reporting. Environment Agency and Defra via GOV.UK EWS
-
Checking F gas equipment for leaks
Guidance
The leak check thresholds and frequencies, and leak detection requirements. Environment Agency EWS
-
Applying for quota to produce or import F gas
Register or apply
Register on the HFC registry and manage quota and authorisations. Environment Agency EWS
-
Qualifications to work with F gas
Guidance
Personnel qualifications and approved company certification bodies. GOV.UK EWS
The law behind this
Questions people ask
How often must F-gas equipment be leak checked?
At least every 12 months from 5 tCO2e, every 6 months from 50 tCO2e and every 3 months from 500 tCO2e of refrigerant, with the interval doubled where a leak detection system is fitted (mandatory at 500 tCO2e). Hermetically sealed systems are exempt below 10 tCO2e. Convert the charge to tCO2e by multiplying the kilograms by the gas's GWP and dividing by 1,000.
Do I need a certificate to work on air conditioning?
Yes. Installing, servicing, leak-checking, recovering gas from or decommissioning equipment containing F-gas requires a personnel qualification, and the business must hold an F-gas company certificate. Equipment owners who use uncertified contractors can be penalised, so check the certificate before any work starts.
Is R404A banned?
New stationary refrigeration using refrigerants with a GWP of 2,500 or more, which includes R404A, has been banned in Great Britain since 2020, and systems of 40 tCO2e or more cannot be serviced with virgin R404A. Reclaimed or recycled R404A can be used for servicing until 2030. Supply will tighten further when quota falls on 1 January 2027, so plan replacements now.
What is changing with F-gas in 2027?
The GB HFC quota falls from 31% to 24% of the baseline on 1 January 2027, a 22.6% cut in the HFCs that can be placed on the market, which typically raises prices for high-GWP refrigerants. Defra decided in May 2026 not to change the phase-down steps in 2026 and will set out its response to the 2025 consultation later. Northern Ireland follows the EU's 2024 Regulation, which adds new bans from 2027.
What are the F-gas penalties?
Civil penalties under the Fluorinated Greenhouse Gases Regulations 2015: a default maximum of £200,000 per breach, £100,000 for most leak-check, certification, recovery and labelling duties, £50,000 for records and reporting failures and £10,000 for certain administrative breaches. The Environment Agency has issued penalties to supermarkets, installers and importers.
Terms used in this guide
- F-gas
- A fluorinated greenhouse gas: hydrofluorocarbons (HFCs), perfluorocarbons (PFCs) or sulphur hexafluoride (SF6), used mainly as refrigerants.
- Global warming potential (GWP)
- How much warming a gas causes compared with the same mass of CO2; R404A is about 3,922, R410A 2,088, R134a 1,430, R32 675.
- Tonnes CO2 equivalent (tCO2e)
- The refrigerant charge in tonnes multiplied by its GWP; the unit used for leak check thresholds and quota.
- HFC quota
- The annual allowance, in tCO2e, that a producer or importer may place on the GB market under the phase-down.
- Company certificate
- The certification a business must hold to install, service or decommission F-gas equipment, issued by bodies such as Refcom or Quidos.
Sources
- Fluorinated gases (F gases), GOV.UK guidance collection
- Checking F gas equipment for leaks, GOV.UK
- Fluorinated Greenhouse Gases Regulations 2015, Schedule 4 (civil penalties)
- Regulation (EU) 517/2014 as retained in GB law
- Defra delays GB F-gas phase down, Cooling Post (May 2026)
- Regulation (EU) 2024/573
Reviewed 14 October 2026. If you spot something out of date, email info@thamesenvironment.com.